SITRANS LUT400 Ultrasonic Level Controller Series

  • Three Versions Available - LUT420, LUT430, LUT440 Choose the model most suited to the application, level of performance and functionality required
  • MCERTS Approved
Product Options

Overview

The Sitrans LUT400 series are a range of compact, single-point, ultrasonic level controllers suitable for long-range continuous level or volume measurement of liquids, slurries and solids. They are also suitable for open channel flow measurement.

There are three versions available to choose from depending on the application, functionality and level of performance required:

  • The SITRANS LUT420 provides level or volume measurement of liquids, slurries and solids. It also benefits from basic pump control functions and logging facilities.
  • The SITRANS LUT430 features the same functions as the LUT420 but also benefits from a full suite of advanced pump control and alarm functionality, open channel flow measurement, and basic flow logging.
  • The SITRANS LUT440 provides high accuracy OCM. It has all the features of the LUT430, plus a full suite of advanced control functionality, enhanced flow logging capabilities and the industry's best accuracy (+/- 1mm within 3 m).

MCERTS

The SITRANS LUT430 and LUT440 are now MCERTS certified meeting the Environment Agency's performance requirements. View downloads for certificate.

Manufactured by: Siemens-Milltronics
Model: SITRANS LUT400 Ultrasonic Level Controller Series

Services offered for this product

  • Sales
  • Rental
  • Installation
  • Calibration
  • Maintenance

Applications

Wet wells
Flumes/weirs
Reservoirs
Chemical storage
Liquid storage
Crusher bins
Dry solids storage

Specification

Mode of Operation Ultrasonic level, volume, pump,
and open channel flow
Measuring range 0.3 - 60 m (1 - 196 ft), transducer dependent
Input
Discrete 0 ... 50 V DC switching level
Logical 0 = < 10 V DC
Logical 1 = 10 ... 50 V DC
Max. 3 mA
Output
Transducer frequency 10 ... 52 kHz
Ultrasonic transducer Compatible transducers: All
EchoMax and ST-H series transducers
Relays • 1 SPDT Form C, NO or NC relay,
rated 1A at 250 V AC, non-inductive and 3A at 30 V DC
• 2 SPST Form A, NO relays, rated
5A at 250 V AC, non-inductive and
3 A at 30 V DC
mA output 4 - 20 mA, isolated
• Max. load 600 Ω max. in ACTIVE mode,
750 Ω max. in PASSIVE mode
• Resolution 0.1 % of range
Accuracy
Error in measurement • Standard operation: ± 1 mm
(0.04 inch) plus 0.17 % of measured distance
• High accuracy OCM: ± 1 mm
(0.04 inch), within 3 m (9.84 ft)
range
Resolution • Standard operation: 0.1 % of
range or 2 mm (0.08 inch), whichever is greater
• High accuracy OCM: 0.6 mm
(0.02 inch), within 3 m (9.84 ft)
range
Temperature compensation -40 ... +150 °C (-40 ... +300 °F)
• Integral temperature sensor in
transducer
• External TS-3 temperature
sensor (optional)
• Programmable fixed
temperature values
Rated operating conditions
Installation conditions  
• Location Indoor/outdoor
• Installation category II
• Pollution degree 4
Ambient conditions  
• Ambient temperature (enclosure) -20 - +50 °C (-4 - +122 °F)
Design
Weight  
• Enclosure with display lid: 1.3 kg (2.87 lbs)
• Enclosure with blank lid: 1.2 kg (2.65 lbs)
Material (enclosure) Polycarbonate
Degree of protection  
• Enclosure with display or blank lid: IP65/Type 4X/NEMA 4X
• Enclosure with blank lid and
knock-out removed:
IP20
• Remote display lid: IP65/Type 3/NEMA 3
Cable
Transducer and mA output signal • Transducer, mA output:
2 copper conductors, twisted,
with foil shield/drain wire, 300 V
0.5 - 0.75 mm² (22 - 18 AWG)
• Relay/power to be copper
conductors per local
requirements to meet 250 V
5 A contact rating
Max. separation between
transducer and transceiver
365 m (1 200 ft)
Displays and controls 60 x 40 mm (2.36 x 1.57 inch)
removable LCD, 240 x 160 pixels
resolution, operational up to 5 m
from enclosure base
Programming  
• Primary 4 Local push buttons
• Secondary • PC running SIMATIC PDM
• PC running Emerson AMS Device
Manager
• PC running a web browser
• PC running a Field Device Tool
(FDT)
• Field Communicator 375/475
(FC375/FC475)
Memory • 512 kB flash EPROM
• 1.5 MB flash for data logging
Power supply
AC version 100 ... 230 V AC ± 15 %,
50/60 Hz, 36 VA
Fuse: 5 x 20 mm, Slow Blow,
0.25 A, 250 V
DC version 10...32 V DC, 10 W
Fuse: 5 x 20 mm, Slow Blow,
1.6 A, 125 V
Certificates and approvals
General CSAUS/C, CE, FM, UL listed,
C-TICK
Hazardous  
• Non-incendive
(Canada)
CSAUS/C Class I, Div. 2, Groups A, B,
C, D; Class II, Div. 2, Groups F, G;
Class III

Downloads

Related products

Certificates